Coil of 152 Meters of Heat Detector Cable, Fixed Temperature 68 degrees Celsius, Black Nylon Coating for Outdoor Applications, with Steel Guide

Skip to product information
1 of 1
  • Polímeros avanzados para detección excepcional de temperatura
  • Conductores tri-metálicos con resistencia extremadamente baja
  • Sistema estructural rígido para soporte de cables
  • Descomposición química a temperaturas fijas específicas
  • Diseño flexible con codos, tees y cruces

Out of stock

Modelo: TC-155NG-500

Proveedor: SAFE FIRE DETECTION INC.

Código SAT: 46191507

Tax included.
Our Commitment ×
By purchasing this product you are making a positive impact. We contribute of each sale and we’ve partnered with WeAreGoodness.io
View full details

SAFE Linear Temperature Detection - Linear Heat Detection (LHD)

Uses advanced polymers and a newly developed alloy to provide exceptional detection, durability and design flexibility. At the core of SafeCable is a twisted pair of extremely low resistance tri-metallic conductors, which are lined with new and advanced thermal polymers. These polymers are chemically designed to decompose at specific fixed temperatures, allowing the stranded conductors to make contact and initiate an alarm.
 

Trays with electrical cables

Trays with electrical cables

A cable tray is an assembly of sections forming a rigid structural system to support cables. These support cables in the same way that bridges support cars and transportation systems. In addition to the straight sections of the tray there are elbows, Tees, crossings and verticals which require a fire detection system that follows the same route as the cables.

Fire detection

Linear Heat Detection (LHD). It is a very effective and low cost solution to protect cable trays. The LHD pigtail can be installed inside the tray with the cables following exactly the same route while being in close proximity to the cables for quick detection.

Electrical Room

Electrical cables lying in the cable tray can be high voltage and can break over time and use. Over time cables can overheat causing fires. Cables in trays that are not properly arranged are more susceptible to catching fire due to access to more oxygen on the surface of the cables.

Characteristics

  • Alarm temperature fixed at 68°C
  • Compatible with any Fire Detection panel
  • Up to 4,572 meters of linear coverage per zone
  • Excellent durability for outdoor environments
  • Multiple alarm temperatures in one zone
  • No need to replace the entire cable after an alarm
  • Approved for up to 10.7 meters of spacing
  • Lowest resistance than any other LHD
  • Guide wire, for easy installation
  • Resistance: 0.164 homs/m
  • Maximum rated voltage: 30VAC, 42Vdc

Important note: Price per 152 meter coil